Please note: Images are for illustrative purposes only.
Features
- True double-conversion online UPS
- Wide input voltage range (110-300 VAC)
- Input power factor correction 0.99
- Output power factor 0.8
- Converter mode available
- ECO mode operation for energy saving (only available for 1-3KVA)
- Hot-swappable battery design only available for 1-3KVA
- Generator compatible
- Adjustable charging current via LCD or software (1A ~ 6A)
- Emergency power off function only available for 6K and up models
MODEL |
ME-3000-WPRU |
|
PHASE |
Single phase with ground |
|
CAPACITY |
3000 VA / 2400 W |
|
INPUT |
|
Voltage Range |
Low Line Transfer |
160 VAC/140 VAC/120 VAC/110 VAC ± 5% (Ambient Temp.<35°C)
(based on load percentage 100% – 80 % / 80 % – 70 % / 70 – 60 % / 60 % – 0) |
Low Line Comeback |
175 VAC /155 VAC/ 135 VAC /125 VAC± 5 % (Ambient Temp.<35°C)
(based on load percentage 100% – 80 % / 80 % – 70 % / 70 – 60 % / 60 % – 0) |
High Line Transfer |
300 VAC ± 5 % |
High Line Comeback |
290 VAC ± 5 % |
Frequency Range |
40Hz ~ 70 Hz |
|
Power Factor |
≧ 0.99 @ nominal voltage |
|
OUTPUT |
|
Output Voltage |
200/208/220/230/240 VAC |
|
AC Voltage Regulation
(Batt. Mode) |
± 1% |
|
Frequency Range
(Synchronized Range) |
47 ~ 53 Hz or 57 ~ 63 Hz |
|
Frequency Range (Batt. Mode) |
50 Hz ± 0.25 Hz or 60Hz ± 0.3 Hz |
|
Current Crest Ratio |
3:1 |
|
Harmonic Distortion |
≦ 3 % THD (Linear Load),
≦ 6% THD (non-linear load) |
|
Transfer
Time |
AC Mode to Batt. Mode |
Zero |
Inverter to Bypass |
4 ms (Typical) |
Waveform (Batt. Mode) |
Pure Sinewave |
|
EFFICIENCY |
|
AC Mode |
90% |
|
Battery Mode |
88% |
|
BATTERY |
|
Battery Type |
12 V / 9Ah |
|
Numbers |
6 |
|
Typical Recharge Time |
4 hours recover to 90% capacity |
|
Charging Current (max.) |
1.0 A |
|
Charging Voltage |
82.1 VDC ± 1% |
|
INDICATORS |
|
LCD Panel |
UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions |
|
ALARM |
|
Battery Mode |
Sounding every 4 seconds |
|
Low Battery |
Sounding every second |
|
Overload |
Sounding twice every second |
|
Fault |
Continuously sounding |
|
PHYSICAL |
|
Dimension, D x W x H (mm) |
630 x 483 x 88 [2U] |
|
Net Weight (kgs) |
29 |
|
ENVIRONMENT |
|
Humidity |
20-90 % RH @ 0- 40°C (non-condensing) |
|
Noise Level |
Less than 50dB @ 1 Meter |
|
MANAGEMENT |
|
Smart RS-232/USB |
Supports Windows 2000/2003/XP/Vista/ 2008, Windows7/8, Linux, Unix, and MAC |
|
Optional SNMP |
Power management from SNMP manager and web browser |
|